8 Appendix
8.1 Technical data
8.1.1 Analog inputs
General information
RTD temperature probe
Measuring circuit monitoring
In the event of an error the digitized output values move to a defined status.
8.1.2 Digital input
Number 8
A/D converter Resolution 16 bit
Designation Standard Measuring range Measuring accu-
racy
1
Ambient
temperature influ-
ence
Pt100 DIN EN 60751 -200 to +850 °C 50 ppm/K
2-wire circuit 0.08 %
Pt500 DIN EN 60751 -200 to +850 °C 50 ppm/K
2-wire circuit 0.08 %
Pt1000 DIN EN 60751 -200 to +850 °C 50 ppm/K
2-wire circuit 0.08 %
Pt100 JIS 1604 -200 to +650 °C 50 ppm/K
2-wire circuit 0.08 %
Pt100 GOST 6651-94 -200 to +850 °C 50 ppm/K
2-wire circuit 0.08 %
Measuring current Pt100 approx. 380 μA, Pt 500, and Pt1000 approx. 150 μA; not con-
stant
Lead compensation A lead resistance can be compensated in the software by correcting
the process value.
1
The accuracy values refer to the maximum measuring range. Smaller measuring ranges lead to reduced lineariza-
tion accuracy.
Measuring element Out of range Probe/cable short
circuit
Probe/cable break
RTD temperature probe Is detected Is detected Is detected
Number 1
Input signal DC 0/24 V
(PLC level; logical “0” = -3 to +5 V; logical “1” = +15 to +30 V)