JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14
36039 Fulda, Germany
Postal address:
36035 Fulda, Germany
Phone: +49 661 6003-0
Fax: +49 661 6003-607
Internet: www.jumo.net
JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow, Essex CM20 2DY, UK
Phone: +44 1279 635533
Fax: +44 1279 635262
Internet: www.jumo.co.uk
JUMO Process Control, Inc.
6733 Myers Road
East Syracuse, NY 13057, USA
Phone: 315-437-5866
1-800-554-5866
Fax: 315-437-5860
Internet: www.jumousa.com
2013-07-09/00529111
Data Sheet 705030 Page 2/7
Technical data
Digital inputs and outputs
Electrical data
Number 12
Digital inputs
Input signal DC 0/24 V
(PLC level; logical ”0“ = -3 to +5 V; logical ”1“ = +15 to +30 V)
Current Max. 5 mA per input
Digital outputs
Output signal DC 0/24 V (depending on external voltage supply)
Current Max. 500 mA per output, short-circuit proof
Voltage supply For module electronics
Connection Lateral (feed via base unit or router module)
Voltage DC 24 V +25/-20 %
Residual ripple 5 %
External voltage supply For digital inputs/outputs
Connection At the front
Voltage DC 24 V +25/-20 % SELV
Current Max. 6 A
Current consumption 90 mA (module electronics only; at DC 19.2 V)
Power consumption 2 W (module electronics only)
Inputs or outputs (terminals 1 to 12) and external voltage
supply (2-pole terminal GND/+24 V)
At the front (removable terminal strips with Push-In technology)
Conductor cross section on terminals 1 to 12
Wire or strand without ferrule Min. 0.14 mm
2
, max. 1.5 mm
2
Strand with ferrule Without plastic collar: Min. 0.25 mm
2
, max. 1.5 mm
2
Strand with ferrule With plastic collar: Min. 0.25 mm
2
, max. 0.5 mm
2
Stripping length on terminals 1 to 12 9 mm
Conductor cross section on terminals GND and +24 V
Wire or strand without ferrule Min. 1.5 mm
2
, max. 2.5 mm
2
Strand with ferrule Min. 1.5 mm
2
, max. 2.5 mm
2
2× strand with twin ferrule
with plastic collar
1.5 mm
2
Stripping length on terminals GND and +24 V 10 mm
Electrical safety Acc. to DIN EN 61010-1
Overvoltage category III, pollution degree 2
Electromagnetic compatibility Acc. to DIN EN 61326-1
Interference emission Class A – only for industrial use –
Interference immunity Industrial requirements
Komentarze do niniejszej Instrukcji