8 Appendix
8.1 General technical data
8.1.1 Directives
2006/95/EC Low Voltage Directive
2004/108/EC Electromagnetic Compatibility Directive
8.1.2 Electrical safety
According to DIN EN 61010-1
Overvoltage category III, pollution degree 2
8.1.3 Protection type according to DIN EN 60529
IP20 modules
Multifunction panel on front IP67, on rear IP20
8.1.4 Protection rating
Overvoltage category III, pollution degree 2
Protection rating I
(with internal isolation to SELV current circuits)
Multichannel controller module
Relay module 4-channel
Protection rating III
Multifunction panel 840
Central processing unit
Router module
Analog input module 4-channel
Analog input module 8-channel
Digital input/output module 12-channel
8.1.5 EMC
Interference emission: Class A – only for industrial use –
Interference immunity: Industry requirement
8.1.6 Voltage supply
DC 24 V (19.2 V to 30 V) SELV
Residual ripple: 5 %
Supply voltage range according to IEC 61131-1 standard: DC 20.4 to 28.8 V